• Versatile design allows custom configurations of branch circuits based on application • Circuit breakers snap-in to Carling's exclusive circuit breaker mounting block, no need to hard wire breakers. • Easy change over from main to generator power by use of slide bar • UL listed to UL67 for AC panel boards • GFI convenience outlet included for service • Panel designed for easy wiring • Front cover easily removed • Handleguards protect breakers • Breaker handles visible through front cover to allow easy breaker status identification • Breaker state can be changed without opening panel • Branch circuits protected by Carling C-Series UL489 listed/VDE approved hy-mag breakers with clip terminals that allow easy snap-in mounting • Breaker trip and Current ratings are unaffected by ambient temperature
Wall mount enclosure,16 gauge cold rolled steel with a powder coat finish
Mains Breaker
2-pole 70 amp mains breaker, 120/240VAC, 50-60 HZ, & 2-pole 70 amp generator back-up breaker, tied together but with independent operation. Slide bar, lockout feature allows transfer from AC to generator power.
Loads
Slots for up to 13 poles of branch circuit breakers. Circuit breakers 1-4, reserved for 2-pole breakers Circuit breakers 5-6 reserved for one 2-pole breaker or two single pole breakers Circuit breaker 7 reserved for a 2 pole 15A breaker (preloaded) for the GFI service outlet & optional surge suppressor Circuit breaker 8 reserved for a single pole circuit breaker
Service Outlet
15 Amp, 120VAC GFI
Operating Voltage
120/240VAC, or 120/208V @ 50/60 Hz, 70 Amps single phase
Service Entry
Service Entry fittings located at the bottom and bottom right corner of the enclosure
Load Center Breakers
UL489 C-Series w/clip terminals & maximum rating of 50 amps per position.